YL-BFK智能型變壓器風冷控制柜
標簽: 智能變壓器風冷控制柜
▍ 簡(jian)要說明(ming) ↴
電(dian)力系(xi)統(tong)由(you)(you)發電(dian)、變(bian)(bian)(bian)(bian)電(dian)、輸電(dian)、配電(dian)幾(ji)個(ge)環節組(zu)成(cheng),其中(zhong)變(bian)(bian)(bian)(bian)壓(ya)(ya)器(qi)(qi)是(shi)一(yi)個(ge)十分(fen)(fen)重(zhong)要(yao)(yao)的(de)(de)(de)(de)元(yuan)件,它的(de)(de)(de)(de)安(an)全運行(xing)對電(dian)力系(xi)統(tong)起著十分(fen)(fen)重(zhong)要(yao)(yao)的(de)(de)(de)(de)作用(yong)(yong)(yong)。變(bian)(bian)(bian)(bian)壓(ya)(ya)器(qi)(qi)在運行(xing)過程中(zhong),繞(rao)組(zu)的(de)(de)(de)(de)銅耗和鐵芯中(zhong)的(de)(de)(de)(de)鐵耗都(dou)轉(zhuan)變(bian)(bian)(bian)(bian)為熱(re)能,使變(bian)(bian)(bian)(bian)壓(ya)(ya)器(qi)(qi)各個(ge)部分(fen)(fen)的(de)(de)(de)(de)溫(wen)度(du)升(sheng)高(gao),變(bian)(bian)(bian)(bian)壓(ya)(ya)器(qi)(qi)的(de)(de)(de)(de)使用(yong)(yong)(yong)壽(shou)命主(zhu)(zhu)要(yao)(yao)由(you)(you)絕緣(yuan)老化(hua)(hua)程度(du)決(jue)定,絕緣(yuan)老化(hua)(hua)主(zhu)(zhu)要(yao)(yao)是(shi)由(you)(you)溫(wen)度(du)變(bian)(bian)(bian)(bian)化(hua)(hua)造成(cheng)的(de)(de)(de)(de)。研(yan)究結果表明:在超越設(she)計(ji)溫(wen)度(du)情況下,溫(wen)度(du)每(mei)升(sheng)高(gao)6度(du),變(bian)(bian)(bian)(bian)壓(ya)(ya)器(qi)(qi)的(de)(de)(de)(de)使用(yong)(yong)(yong)壽(shou)命就(jiu)要(yao)(yao)減少(shao)一(yi)半,這便是(shi)變(bian)(bian)(bian)(bian)壓(ya)(ya)器(qi)(qi)絕緣(yuan)老化(hua)(hua)的(de)(de)(de)(de)六度(du)法則。由(you)(you)此可見溫(wen)度(du)是(shi)影響變(bian)(bian)(bian)(bian)壓(ya)(ya)器(qi)(qi)使用(yong)(yong)(yong)壽(shou)命的(de)(de)(de)(de)一(yi)個(ge)重(zhong)要(yao)(yao)指標。
YL-BFK智(zhi)能型變壓器風冷控(kong)制柜就是針對這三種冷(leng)卻方式而設(she)計的微機型(xing)控制柜。變(bian)壓(ya)器(qi)風(feng)冷(leng)控制柜可以(yi)實現(xian)遠方自動和(he)就地手動控制方式,并可以(yi)把各種信息上傳(chuan)顯示和(he)下行控制設(she)定,對變(bian)壓(ya)器(qi)整個冷(leng)卻系統實現(xian) 優智能控制,變(bian)壓(ya)器(qi)風(feng)冷(leng)控制柜達(da)到節能和(he)延(yan)長變(bian)壓(ya)器(qi)使用(yong)(yong)壽命的目的,節約人力和(he)檢修維(wei)護費用(yong)(yong)。
▍ 遵(zun)循標準(zhun) ↴
● GB1094-2013 電力變(bian)壓器
● GB2900-1995 電工術語
● GB2536-2011 變壓(ya)器油
● GB/T13499-2002 電力變(bian)壓器應用導則
● GB/T17468-2008 電力變壓器選(xuan)用原(yuan)則
● JB/T3837-2010 變壓器類產品型(xing)號編制方法
● DL/T572-2010 電力變壓器(qi)運(yun)行規程
● DL/T5147-2001 電力系統安全自(zi)動裝置設(she)計技術規定
● GB/T2682-1981 低壓成套設(she)備(bei)中的(de)指(zhi)示燈和(he)按鈕顏(yan)色(se)
● GB7251-2013 低壓成套開關設(she)備和控制設(she)備
● DL/T720-2013 電(dian)力系統繼電(dian)保護柜、屏通(tong)用技術(shu)條件(jian)
● DL/T5136-2012 火力(li)發電廠、變電所(suo)二次(ci)接線(xian)設計(ji)技(ji)術規(gui)程
● GB50054-2011 低(di)壓(ya)配電設計規范(fan)
▍ 技術(shu)參數 ↴
▍ 技術(shu)參數 ↴
✔ 適(shi)用范圍:110kV、220kV、330kV、500kV、750kV及以上(shang)的油浸變壓器(qi)
✔ 安裝方式:戶外落地式、壁掛式
✔ 工作電(dian)源:三相四(si)線交(jiao)流(liu)雙路電(dian)源輸入AC380V±15%
✔ 控制電源:直流(liu)輸入DC220V±10%
✔ 海(hai)拔高度:3000米以下
✔ 環境溫度:-40℃~+85℃
✔ 相對濕度:≤95%RH
✔ 大風速:≤35m/s
✔ 防護等(deng)級:IP55
▍ 型號說明 ↴
▍ 型號說明 ↴
▍ 原理功能 ↴
▍ 原理功能 ↴
YL-BFKW智能型變壓器風(feng)冷控(kong)制柜(ju)采用了(le)SIMENS的(de)可(ke)編程控(kong)制器作為(wei)(wei)主要的(de)控(kong)制核心,觸(chu)摸屏作為(wei)(wei)人(ren)機界面,交(jiao)流(liu)接(jie)(jie)觸(chu)器作為(wei)(wei)功率(lv)執行元件,斷路(lu)器、相序缺相繼電器作為(wei)(wei)保護元件,通過觸(chu)摸屏設置運行參數(shu),根據頂層油(you)溫(wen)和運行負荷(he)信號投入和退出相應模(mo)式的(de)冷卻器,將(jiang)運行中(zhong)的(de)故障信息通過通訊(xun)口(kou)或(huo)故障接(jie)(jie)點遠傳,同時將(jiang)信息整理(li)存儲于觸(chu)摸屏,也(ye)可(ke)定(ding)時自(zi)動輪換工作電源和冷卻器運行模(mo)式。智能型變壓器風冷控制柜實現了控制自動化、狀態信息化、顯示與操作人性化。
》備(bei)用(yong)電(dian)源自投
雙(shuang)電(dian)(dian)(dian)源(yuan)供(gong)電(dian)(dian)(dian)且(qie)互為備用,I段或II段電(dian)(dian)(dian)源(yuan)消失(shi),備用電(dian)(dian)(dian)源(yuan)自動(dong)投入,同時(shi)發出“I電(dian)(dian)(dian)源(yuan)故(gu)(gu)障”或“II電(dian)(dian)(dian)源(yuan)故(gu)(gu)障”的遠方信(xin)號,就近顯(xian)示故(gu)(gu)障內容。故(gu)(gu)障修復后(hou)信(xin)號消失(shi),同時(shi)保(bao)存故(gu)(gu)障記錄。
》按溫度和(he)負荷起停冷(leng)卻(que)器
運(yun)(yun)行中的變(bian)壓(ya)器上(shang)(shang)層油溫高于55度(du)(用(yong)戶整定(ding))或(huo)變(bian)壓(ya)器保護屏上(shang)(shang)電(dian)(dian)流繼電(dian)(dian)器動作(80%負荷用(yong)戶整定(ding)),“輔(fu)助(zhu)”狀態(tai)冷(leng)(leng)卻器投(tou)(tou)入運(yun)(yun)行,當(dang)溫度(du)降至45度(du),“輔(fu)助(zhu)”狀態(tai)的冷(leng)(leng)卻器退(tui)出(chu)運(yun)(yun)行。如(ru)運(yun)(yun)行中“工(gong)作”或(huo)“輔(fu)助(zhu)”狀態(tai)的任(ren)何(he)一組(zu)發(fa)生故(gu)(gu)障(zhang),“備用(yong)”冷(leng)(leng)卻器投(tou)(tou)入運(yun)(yun)行,同時(shi)發(fa)出(chu)“冷(leng)(leng)卻器故(gu)(gu)障(zhang)”的遠方信號,就(jiu)近(jin)顯(xian)示故(gu)(gu)障(zhang)內(nei)容。修(xiu)復(fu)故(gu)(gu)障(zhang)后,“備用(yong)”狀態(tai)的冷(leng)(leng)卻器退(tui)出(chu)運(yun)(yun)行,故(gu)(gu)障(zhang)信號消(xiao)失,同時(shi)保存故(gu)(gu)障(zhang)記錄。
》冷卻(que)器全停延時跳閘
變(bian)壓器(qi)運(yun)行時(shi),I、II段電(dian)源消(xiao)失(shi)及所有冷卻器(qi)退出(chu)運(yun)行,發出(chu)“冷卻器(qi)全停故障”遠方信號(hao),同(tong)時(shi)啟動20分鐘和60分鐘延時(shi)跳閘,當主(zhu)變(bian)上層(ceng)油(you)溫(wen)高于70度時(shi)(用戶整定(ding)),20分鐘后跳閘出(chu)口(kou);當主(zhu)變(bian)上層(ceng)油(you)溫(wen)低(di)于70度時(shi)(用戶整定(ding)),60分鐘后跳閘出(chu)口(kou)。
》冷卻(que)器(qi)模(mo)式(shi)定時輪換
電(dian)機運(yun)行(xing)(xing)在(zai)60℃~70℃環(huan)境(jing)溫度下極(ji)易(yi)造成(cheng)“工作”組(zu)風扇電(dian)機軸承油脂過早劣(lie)化,造成(cheng)此(ci)組(zu)風扇電(dian)機經(jing)常燒毀,為此(ci)設(she)計了冷卻(que)器運(yun)行(xing)(xing)模(mo)式(shi)定(ding)時輪換(huan)功能,按照觸摸屏設(she)置的時間(jian),定(ding)時自動輪換(huan)冷卻(que)器運(yun)行(xing)(xing)模(mo)式(shi),令每組(zu)冷卻(que)器交替運(yun)行(xing)(xing)在(zai)“工作”模(mo)式(shi)。
》動(dong)力(li)電源定時輪換
I、II段動力(li)電源能按照觸摸屏設置(zhi)的(de)時間進行定時輪換(huan)使用(yong)。
》冷卻(que)器啟(qi)動
多(duo)組(zu)冷(leng)(leng)卻器(qi)(qi)(qi)(qi)按變壓運行的(de)需要分配為“工作”、“備用(yong)”、“輔(fu)助”狀態(tai);變壓器(qi)(qi)(qi)(qi)運行時(shi)(shi),“工作”狀態(tai)的(de)冷(leng)(leng)卻器(qi)(qi)(qi)(qi)投入運行,如(ru)果任何(he)一組(zu)“工作”狀態(tai)的(de)冷(leng)(leng)卻器(qi)(qi)(qi)(qi)發生(sheng)故(gu)障(zhang),處在(zai)“備用(yong)”狀態(tai)冷(leng)(leng)卻器(qi)(qi)(qi)(qi)投入運行,同時(shi)(shi)發出(chu)“冷(leng)(leng)卻器(qi)(qi)(qi)(qi)故(gu)障(zhang)”的(de)遠(yuan)方信(xin)號,就近顯示故(gu)障(zhang)內容。修(xiu)復故(gu)障(zhang)后(hou),“備用(yong)”狀態(tai)冷(leng)(leng)卻器(qi)(qi)(qi)(qi)退(tui)出(chu)運行,故(gu)障(zhang)信(xin)號消失,同時(shi)(shi)保存故(gu)障(zhang)記錄。
》故障(zhang)告(gao)警
冷控(kong)柜檢測(ce)到(dao)故障(zhang)時會發(fa)出告警信號:I段(duan)電(dian)源故障(zhang),II段(duan)電(dian)源故障(zhang),冷卻(que)器故障(zhang),冷卻(que)器全停故障(zhang),控(kong)制(zhi)電(dian)源消(xiao)失或PLC故障(zhang)等。報警形(xing)式為:無源接點和串行通訊兩種(zhong)形(xing)式。
》故障記錄和信息查(cha)詢(xun)
觸摸屏完成了參數設置(zhi)功能之外還可以記錄故(gu)障(zhang)(zhang)發生(sheng)的具體內(nei)(nei)容,如(ru):故(gu)障(zhang)(zhang)發生(sheng)時間(jian),故(gu)障(zhang)(zhang)恢復時間(jian),故(gu)障(zhang)(zhang)內(nei)(nei)容。點擊故(gu)障(zhang)(zhang)內(nei)(nei)容欄(lan)還可以看(kan)到故(gu)障(zhang)(zhang)內(nei)(nei)容分(fen)析。
》箱內(nei)溫濕(shi)度(du)自動控制
安裝了(le)溫(wen)(wen)濕度控制器,根據箱(xiang)內的環境溫(wen)(wen)度和(he)濕度自動控制水分含(han)量和(he)空氣溫(wen)(wen)度。
》(選配)機柜空調功(gong)能(neng)
在(zai)惡劣的環境(jing)下,保證系(xi)統能(neng)在(zai)正常的溫濕度(du)(du)環境(jing)下正常的工作,提高系(xi)統的可靠性(xing)和(he)穩定性(xing)。一體化結構設計(ji),專業除濕功(gong)能(neng),有(you)效降(jiang)低(di)控制柜內的相(xiang)對濕度(du)(du),可靠性(xing)高,不(bu)間斷運行(xing)10年以上(shang)。
》(選(xuan)配)遠程集(ji)控(kong)(kong)中(zhong)心多臺(tai)監控(kong)(kong)
通(tong)過(guo)西門子(zi)S7-200smart系列PLC的網(wang)(wang)絡(luo)連(lian)接(jie)功(gong)能實(shi)(shi)現(xian)多臺設備組網(wang)(wang),并(bing)在(zai)遠(yuan)端實(shi)(shi)現(xian)對(dui)設備的監控(kong)。
》(選配(pei))帶有變(bian)頻器調(diao)速功能
通(tong)過變頻器的頻率變化(hua)控制(zhi)風機轉速快慢,使(shi)該系(xi)統(tong)具有節能(neng)降耗、低噪環保、控制(zhi)溫升范圍、提高(gao)絕緣壽命等特點(dian)。
▍ 外形尺寸(cun) ↴
通(tong)過變(bian)頻(pin)器的頻(pin)率(lv)變(bian)化控制(zhi)風機(ji)轉速(su)快慢,使該(gai)系統(tong)具有節(jie)能(neng)降耗、低噪環保、控制(zhi)溫升(sheng)范圍、提高絕緣壽命等特點。
寬度W |
深度D |
高度H |
600-800mm |
500-700mm |
1500-1700mm |
▍ 質量保證(zheng) ↴
▍ 客(ke)戶安裝實景拍攝 ↴
▍ 訂貨須知 ↴
● 請提(ti)供(gong)變(bian)壓器冷(leng)卻方式
● 請提供冷卻器組數
● 請提(ti)供油(you)泵、冷卻(que)風(feng)機個數及功率
● 如需遠方控制請(qing)提供控制要求
● 如需(xu)精準(zhun)控制請提供溫度和負(fu)載的模擬量
● 特(te)殊工(gong)況控制(zhi)可根據用戶(hu)特(te)殊要求進行(xing)加工(gong)制(zhi)作
▍ 售(shou)后服(fu)務承諾 ↴
● 公(gong)司負責(ze)將用戶所訂購的(de)設備免(mian)費調試及現場指導(dao)安裝(zhuang)直(zhi)至(zhi)正常(chang)運行。
● 公(gong)司(si)在安(an)裝現場(chang)免(mian)費為用戶提供(gong)基礎操作、日常保養的培(pei)訓(xun)服務。
● 公司自設備正常運行之日(ri)起(qi)按本公司標準保(bao)修條例對項目的設備提供保(bao)修服(fu)務。
● 保修期(qi)外的設備僅按成(cheng)本(ben)價收取故(gu)障配件(jian)費,免人(ren)工費。
● 公司服(fu)務響(xiang)應時間為2小時內(nei),陜西省內(nei)1個(ge)工(gong)(gong)作日內(nei)到達現(xian)場,外省用戶2個(ge)工(gong)(gong)作日到達現(xian)場。
● 公(gong)司(si)將免費提供系(xi)統及(ji)硬件設備(bei)的(de)升(sheng)級(ji)和技術咨詢(xun)。
● 公司將定期向用(yong)戶(hu)贈送產品技術相(xiang)關資料,不定期上門或電話(hua)回訪用(yong)戶(hu),了(le)解系統及設備的運行情況,現場解決(jue)用(yong)戶(hu)的問(wen)題。
意聯(lian)電氣廠家專業生產(chan)智能型變壓器(qi)風冷控制柜,變壓(ya)器冷(leng)卻控(kong)制柜,產品選型豐富(fu),廠家價(jia)格,專業(ye)電(dian)測10年,找變壓(ya)器風冷(leng)智(zhi)能控(kong)制柜,變壓(ya)器冷(leng)卻控(kong)制柜,選意聯電(dian)氣(qi),打造電(dian)力精(jing)品。