電纜斷了怎么找到斷點[實用方法]
標簽: 電纜故障測試儀 電纜故障測試儀是一套綜合性的電纜故障探測儀器。能對電纜的高阻閃絡故障,高低阻性的接地,短路和電纜的斷線,接觸不良等故障進行測試,若配備聲測法定點儀,可準確測定故障點的準確位置。特別適用于測試各種型號、不同等級電壓的電力電纜及通信電纜。電纜斷了怎么找到斷點那?意聯電氣闡述電纜故障的種類與判斷方法及電纜故障點的主要查找方法,實用的找斷點方法。
一、電纜故障的種類與判斷
無論(lun)是高壓電纜或低壓電纜,在施工安裝、運(yun)行過程中經常因(yin)短路、過負荷運(yun)行、絕緣老化或外力損壞等原因(yin)造(zao)成故障(zhang)。電纜故障(zhang)分為接(jie)地、短路、斷(duan)線(xian)三類。
三(san)芯電纜故障類(lei)型(xing)主要有以(yi)下幾方面:一(yi)芯或兩(liang)芯接觸;二(er)相芯線(xian)(xian)間短路;三(san)相芯線(xian)(xian)完全短路;一(yi)相芯線(xian)(xian)斷(duan)(duan)線(xian)(xian)或多相斷(duan)(duan)線(xian)(xian)。 對(dui)(dui)于(yu)直(zhi)接短路或斷(duan)(duan)線(xian)(xian)故障用萬用表(biao)可直(zhi)接測(ce)量(liang)判斷(duan)(duan),對(dui)(dui)于(yu)非直(zhi)接短路和接池故障,用兆歐(ou)表(biao)遙測(ce)芯線(xian)(xian)間絕緣(yuan)電阻或芯線(xian)(xian)對(dui)(dui)地絕緣(yuan)電阻,根據其阻值(zhi)可判定故障類(lei)型(xing)。
二、電纜故障點(dian)的查(cha)找(zhao)方法
A、電橋法
電橋法就是雙臂電橋測出電纜芯線的直流電阻值,再準確測量電纜實際長度,按照電纜長度與電阻的正比例關系,計算的故障點。該方法對于電纜芯線間直接短路或短路點接觸電阻小于1Ω的故障,判斷誤差一般不大于3m,對于故障點接觸電阻大于1Ω的故障,可采用加高電壓燒穿的方法使電阻降至1Ω以下,再按此方法測量。
測量電路首先測出芯線a與b之間的電阻R1,則R1=2RX+R,其中R為a相或b相至故障點的一相電阻值,R為短接點的接觸電阻。再就電纜的另一端測出a’和b’芯線間的直流電阻值R2,則R2=2R(L-X)+R,式中R(L-X)為a’相和b’相芯線至故障點的一相電阻值。測完R1與R2后,再按圖3所示電路將b’與C’短接,測出b、c兩相芯線間的直流電阻值,則該阻值的1/2為每相芯線的電阻值,用RL表示。RL=RX+R(L-X),由此可得出故障點的接觸電阻值:R=R1+R2-2RL。因此,故障點兩側芯線的電阻值可用下式表示:RX=(R1-R)/2,R(L-X)=(R2-R)/2。RX、R(L-X)、RL三個數值確定后,按比例公式即可求出故障點距電纜端頭的距離X或(L-X):X=(RX/RL)L,(L-X)=(R(L-X)/RL)L,式中L為電纜的總長度。 采用電橋法時應保證測量精度,電橋連接線要盡量短,經徑要足夠大,與電纜芯線連接要采用壓接或焊摟,計算過程中小數位要全部保留。
B、電容電流測定法
(1)首先在電纜首端分別測出每芯線的電容電流(應保持施加電壓相等)Ia、Ib、Ic的數值。
(2)在電纜的末端再測量每相芯線的電容電流Ia’、Ib’、Ic’的數值,以核對完好芯線與斷線芯線的比容之比,初步可判斷出斷線距離近似點。
(3)根據電容量計算公式C=1/2πfU可知,在電壓U、頻率f不變時C與I成正比;因為工頻電壓的f(頻率)不變,測量時只要保證施加電壓不變,電容電流之比即為電容量之比。設電纜全長L,芯線斷線點距離為x,則Ia/Ic=L/x,x=(Ic/Ia)L。測量過程中,只要保證電壓不變,電流表讀數準確,電纜總長度測量準確,其測定誤差比較小。
C、零電位法
(a)先在b和c相芯線上接上電池E,再在地面上敷設一根與故障電纜長度相等的比較導線S,該導線要用裸銅線或裸鋁線,其截面應相等,不能有中間接頭。
(b)將微伏表的負極接地,正極接一根較長的軟導線,導線另一端要求在敷設的比較導線上滑動時能充分接觸。
(c)合上(shang)閘(zha)刀開(kai)關K,將軟導線(xian)的斷(duan)頭在比較(jiao)導線(xian)上(shang)滑動,當微伏表指示為零時的位置(zhi)即為電纜故(gu)障點的位置(zhi)。
D、測聲法
所(suo)謂測聲(sheng)法(fa)就是(shi)根(gen)據故障電(dian)(dian)(dian)(dian)纜(lan)(lan)放(fang)電(dian)(dian)(dian)(dian)的聲(sheng)音(yin)進(jin)行查(cha)找,該方法(fa)對于高壓(ya)(ya)電(dian)(dian)(dian)(dian)纜(lan)(lan)芯線(xian)對絕緣(yuan)層(ceng)閃絡(luo)放(fang)電(dian)(dian)(dian)(dian)較為(wei)有效。此方法(fa)所(suo)用設備(bei)為(wei)直流(liu)耐(nai)壓(ya)(ya)試(shi)驗機(ji)。電(dian)(dian)(dian)(dian)路接線(xian)如圖1所(suo)示, 其中SYB為(wei)高壓(ya)(ya)試(shi)驗變壓(ya)(ya)器,C為(wei)高壓(ya)(ya)電(dian)(dian)(dian)(dian)容器,ZL為(wei)高壓(ya)(ya)整流(liu)硅堆,R為(wei)限(xian)流(liu)電(dian)(dian)(dian)(dian)阻,Q為(wei)放(fang)電(dian)(dian)(dian)(dian)球間隙,L為(wei)電(dian)(dian)(dian)(dian)纜(lan)(lan)芯線(xian)。當(dang)電(dian)(dian)(dian)(dian)容器C充(chong)電(dian)(dian)(dian)(dian)到(dao)一定(ding)電(dian)(dian)(dian)(dian)壓(ya)(ya)值時(shi),球間隙對電(dian)(dian)(dian)(dian)纜(lan)(lan)故障芯線(xian)放(fang)電(dian)(dian)(dian)(dian),在故障處電(dian)(dian)(dian)(dian)纜(lan)(lan)芯線(xian)對絕緣(yuan)層(ceng)放(fang)電(dian)(dian)(dian)(dian)產生"滋(zi)、滋(zi)"的火花放(fang)電(dian)(dian)(dian)(dian)聲(sheng),再在雜噪(zao)聲(sheng)音(yin) 小的時(shi)候(hou),借助(zhu)耳聾助(zhu)聽(ting)(ting)器或醫用聽(ting)(ting)診(zhen)器等音(yin)頻放(fang)大設備(bei)進(jin)行查(cha)找。查(cha)找時(shi),將(jiang)拾音(yin)器貼(tie)近地面,沿電(dian)(dian)(dian)(dian)纜(lan)(lan)走向(xiang)慢慢移(yi)動,當(dang)聽(ting)(ting)到(dao)"滋(zi)、滋(zi)"放(fang)電(dian)(dian)(dian)(dian)聲(sheng) 大時(shi),該處即為(wei)故障點。使用該方法(fa)一定(ding)要(yao)注意安全,在試(shi)驗設備(bei)端和電(dian)(dian)(dian)(dian)纜(lan)(lan)末端應設專人(ren)監看。
要測出電線電纜斷點,可以(yi)參考今天介紹的幾種(zhong)方法,我們(men)在(zai)有條件的情況下(xia),還是(shi)借助(zhu)儀器設備(bei)提高工(gong)作(zuo)效率(lv)比較好。